Steel
duct cladding
The steel ventilation and smoke outlet duct systems protected by MONOLUX® board are designed to provide a fire resistance of up to
240 minutes. Below are systems available for MONOLUX®
self supporting duct systems. |
| |
Fire resistance (BS 476: Part 24: 1987)
|
Board thickness
(mm) |
Dimensions of duct
(mm) |
Rock wool
(thickness x density) |
Stability &
integrity
(minimum)
|
Insulation
(minimum) |
|
240 |
- |
25 |
Up to
6000 wide x 1500 high |
- |
|
240 |
240 |
25 |
Up to
6000 wide x 1500 high |
100mm x 100kg/m³ |
|
120 |
- |
16 |
Up to
6000 wide x 1500 high |
- |
|
120 |
120 |
16 |
Up to
6000 wide x 1500 high |
50mm x 100kg/m³ |
|
120 |
120 |
19 |
Up to
6000 wide x 1500 high |
50mm x 80kg/m³ |
|
60 |
60 |
16 |
Up to
6000 wide x 1500 high |
35mm x 45kg/m³
or 25mm x 50kg/m³ |
|
|
Minimum sizes of steel sheet, stiffeners
and sizes of angle sections are as
specified in DW144 Guide to construction
of sheet metal ducts or SMACNA Guide. The steel ducts must be constructed with rolled steel angle-flanged cross joints. Longitudinal seams formed by using the Pittsburgh lock are recommended.
|
|
MONOLUX® 40 boards, thickness in
accordance with the table above. |
|
Galvanised steel hanger support system,
Maximum stress levels should not exceed
10N/mm²
or 6N/mm² for two and four hour
systems respectively. |
|
Galvanised steel angle at corner, 50mm x
50mm x 0.6mm. |
|
Steel channel support folded around at
610mm centres, 50mm x 35mm x 0.6mm. |
|
Steel channel support folded around at
610mm centres, 50mm x 35mm x 0.6mm for
two hours and 100mm x 50mm x 0.6mm for
four hours. |
|
Mild steel angle support at 1220mm centres,
40mm x 40mm x 5mm. |
|
Mild steel angle support at 1220mm centres,
40mm x 40mm x 5mm for two hours and
50mm x 50mm x 5mm thick for four hours. |
|
Rock wool packing to fill penetration seal
gap between MONOLUX® duct cladding and
compartment wall or floor. |
|
Rock wool, thickness and density in
accordance with the table above. |
|
MONOLUX® 40 boards forming collar at any
penetration through wall or floor, minimum
100mm x 100mm, with 19mm thickness for
two hours and 25mm thickness for four hours. |
|
Self tapping screws at 200mm centres. |
|
Compartment wall or floor. |
|
Galvanised steel hanger support system,
maximum stress levels should not exceed
15N/mm². |
|
Rock wool, 25mm thick x 50kg/m3. |
|
MONOLUX® 40 boards forming collar at any
penetration through wall or floor, minimum
100mm x 100mm x 19mm thick. |
|
|
|

120 and
240 minute cladding enclosure
|
|
|
|

120 and
240 minute insulated cladding enclosure
|
|
|
* For more detail, roll your
cursor over the individual numerals in the
two drawings
above.
Note:
Additional items for
consideration where
ducts exceed 2000mm
width or 1500mm depth:
|
Back to
previous page....