Up to 240 minutes stability, integrity and insulation cladding sheet metal ducts.

Fire resistance (BS 476: Part 24: 1987)
Board thickness
(mm)
Dimensions of duct
(mm)
Rock wool
(thickness x density)
Stability & integrity (minimum)
 Insulation
(minimum)
240 - 25 Up to 6000 wide x 1500 high -
240 240 25 Up to 6000 wide x 1500 high 100mm x 100kg/m³
120 - 16 Up to 6000 wide x 1500 high -
120 120 16 Up to 6000 wide x 1500 high 50mm x 100kg/m³
120 120 19 Up to 6000 wide x 1500 high 50mm x 80kg/m³
60 60 16 Up to 6000 wide x 1500 high 35mm x 45kg/m³ or 25mm x 50kg/m³
MONOLUX® 40 boards, thickness in accordance with the table above.
Galvanised steel duct.
Galvanised steel hanger support system, maximum stress levels should not exceed 15N/mm².
Galvanised steel angle at corner, 50mm x 50mm x 0.6mm.
Steel channel support folded around at 610mm centres, 50mm x 35mm x 0.6mm.
Mild steel angle support at 1220mm centres, 40mm x 40mm x 5mm.
Rock wool packing to fill penetration seal gap between MONOLUX® duct cladding and compartment wall or floor.
Rock wool, 25mm thick x 50kg/m3.
MONOLUX® 40 boards forming collar at any penetration through wall or floor, minimum 100mm x 100mm x 19mm thick.
Self tapping screws at 200mm centres.
Compartment wall or floor.





60 minute insulated cladding enclosure

*  For more detail, roll your cursor over the individual numerals in the above drawing.

Note:

Additional items for consideration where ducts exceed 2000mm width or 1500mm depth:

  • The ducts should be installed incorporating additional threaded rods internally to act as stiffeners. These rods should be installed such that the maximum unsupported distance does not exceed 1200mm.
     