specifications |
Thickness |
20mm, 25mm, 30mm, 35mm,
40mm, 45mm, 50mm, 55mm or 60mm
|
|
Widths |
610mm or 1220mm
|
|
Lengths |
1220mm
|
|
Thickness tolerance |
-0.8mm, +0.0mm
|
|
Length tolerance |
0.0mm +4.8mm
|
|
Width tolerance |
-0.0mm, +4.8mm
|
|
|
NEWTHERM® P is
a rigid board but edges and corners should
be protected where impact damage may occur.
The large range of thickness available allows selection of the most
economical board to meet given periods of fire resistance.
All board sizes are based on metric equivalents of imperial
dimensions rounded to the nearest 5mm.
Non-standard sizes available to order. Standard sizes and board
tolerances are shown above.
|
|
Product performance
|
Mechanical
Flexural strength
Nominal Dry Density
|
|
2.0MPa
500kg/m³
|
Fire
Non-combustible to BS 476: Part 4: 1970
|
|
Yes |
Material of limited combustibility as defined in local Building Regulations
|
|
Yes |
Classification of surface as defined in local Building Regulations
|
|
Class 0
|
Spread of flame to BS 476: Part 7: 1987
|
|
Class 1
|
Moisture
Moisture movement (35-85%RH)
|
|
0.03%
|
Weight
Nominal board weights at ambient conditions |
|
20mm
25mm
30mm
35mm
40mm
45mm
50mm
55mm
60mm
|
10.3kg/m²
12.9kg/m²
15.5kg/m²
18.1kg/m²
20.6kg/m²
23.2kg/m²
25.8kg/m²
28.4kg/m²
30.9kg/m²
|
|
| |
| |
|

Cross section view
|
|
1) |
Steel dry or wet riser pipe. |
|
2) |
NEWTHERM® P board protection,
thickness as per required fire resistance.
|
|
3) |
Mineral wool insulation, thickness and density as per required fire resistance.
|
|
4) |
Hanger rods (left unprotected if stress does not exceed 10N/mm² for 120 minutes fire rating
and 6N/mm² for 240 minutes fire rating).
|
|
5) |
Steel angle at corners.
|
|
6) |
Steel angle forming a good fit around pipe.
|
|
7) |
Transverse joint backed with steel angle.
|
|
8) |
Gaps at transverse joint and at hanger rod penetration to be filled with
INTUMEX® AN Sealant.
|
|

Isometric view
|
|