SUPALUX® - Industrial lining email
home

The fire resistance requirements for external walls depend on the type and size of the building. The minimum periods of fire resistance for the elements of structure in an industrial building can be found in the local building cod. In addition, the fire resistance requirement for external walls is determined by the distance of the wall from any relevant boundary. Where any part of the external wall is less than 1 meter from any point on a relevant boundary, the designer must consider fire exposure from each side of the wall separately; where the external walls is 1 meter or more from any relevant boundary fire exposure is only considered from inside the building.

SUPALUX® Industrial Lining is a strong, fire rated exposed or conceal grid system designed to provide fire resistance of up to 240 minutes to external wall of portal framed light industrial units.

* For more detail, roll your cursor over the individual numerals in the drawings below.


0.6mm thick profile steel cladding.
125mm x 50mm x 3mm thick channel sheeting rail at 2200mm centres.
25mm x 25mm x 0.4mm thick steel angle fixed to channels using one number No.8 self-tapping screw per leg.
25mm x 50mm x 25mm x 0.4mm thick steel channel at 610mm centres
9mm thick SUPALUX® cover strip 75mm wide.
25mm x 25mm x 0.91mm thick top and bottom angle.
9mm thick SUPALUX® fixed to channels and cover strips using 19mm long No.8 self-tapping at 300mm centres Steel channels forming framing 100mm x 70mm x 100mm x 0.9mm.
A - B 610mm
B - C 610mm
C - D 610mm
C - D 610mm

  240 minute fire rated SUPALUX® industrial lining
 


NOTES:

  • For fire resistance where insulation in excess of 15 minutes is required for this application, please consult Intumex Asia Pacific.