Structural steel protection

The level of fire resistance required for columns and beams depends on the purpose group and size of the building and this can be found in the local building code. Any column or beam must have at least the fire resistance required for any other element of structure to which it provides support (whether that other element is loadbearing or not).

Any column or beam forming part of more than one building or compartment must have a fire resistance which is the greater of the relevant requirements.

SUPALUX® can be used to provide up to 120 minutes fire resistance to structural steelwork. The board can be screwed directly to a light gauge steel frame to form encasements.
 

0.6mm thick profile steel cladding
125mm x 50mm x 3mm thick channel sheeting rail at 2200mm centres
25mm x 25mm x 0.4mm thick steel angle fixed to channels using one number No.8 self-tapping screw per leg
25mm x 50mm x 25mm x 0.4mm thick steel channel at 610mm centres
9mm thick SUPALUX® cover strip 75mm wide
25mm x 25mm x 0.91mm thick top and bottom angle
9mm thick SUPALUX® fixed to channels and cover strips using 19mm long No.8 self-tapping at 300mm centres
610mm (from A to B)
610mm (from B to C)
610mm (from C to D)


120 minute fire rated SUPALUX® 3-sided structural steel beam protection

1) SUPALUX® board
2) Structural steel beam
3)

25mm x 25mm x minimum 0.65mm thick steel angle fixed to floor with 3.7mm diameter x 32mm long shot fired nails at 400mm centres.

4)

75mm wide SUPALUX® cover strips of same thickness as casing, fixed on both sides of the joint with No.8 self-tapping screws at 160mm centres

5)

Soffit

NOTE:

  • The thickness of the SUPALUX® board is determined by the Hp/A factor of the steel section to be clad. Please consult Intumex Asia Pacific for a full table of Hp/A and section factor tables.





120 minute fire rated SUPALUX® 4-sided structural steel column protection


1) SUPALUX® board
2) Structural steel column
3)

25mm x 25mm x minimum 0.65mm thick steel angle

4)

75mm wide Supalux® cover strips of same thickness as casing, fixed on both sides of joint with No.8 self-tapping screws at 160mm centres.

NOTES:

  • The thickness of the SUPALUX® board is determined by the Hp/A factor of the steel section to be clad. Please consult Intumex Asia Pacific for a full table of Hp/A and section factor tables.