One or two layers of VERMICULUX® board (see TABLE 3 for thickness) screwed face to edge at 200mm centres.

Cover strips
VERMICULUX® 25mm thick x 125mm wide, fixed over joints.

For single layer duct constructions, cover strips should be fixed to the external faces of the top and sides, the bottom strip must be inside the duct.

For double layer constructions, board joints are staggered minimum 100mm and cover strips need only to be fixed to the inside at the bottom of the duct. Cables should be supported on trays but these can be omitted if the bottom internal cover strip are located at no more than 600mm centres.

Supports
M10 threaded rods fixed by means of expansion bolts into the concrete soffit. Tensile stress in rods should not exceed 6N/mm2.

 

VERMICULUX® boards can provide up to 90 minutes of fire resistance level (FRL) for cables and services enclosure with external fire exposure in accordance with the criteria of BS476: Part 20: 1987 thereby maintaining the functionality of essential cables in a fire.

TABLE 3

Required FRL/Thickness of board for cable enclosure

FRL 30 minutes 60 minutes 90 minutes
Type 1 dimension 100mm x 100mm
Thickness 30mm 50mm or 2 x 25mm 2 x 35mm
Type 2 dimension 350mm x 170mm to 760mm x 300mm
Thickness 25mm 45mm or 20+25mm 2 x 30mm
 