Casing
One or two layers of VERMICULUX®
board
(see TABLE 3 for thickness) screwed
face to edge at 200mm centres.
Cover strips
VERMICULUX®
25mm thick x 125mm
wide, fixed over joints.
For single layer duct
constructions, cover strips should be fixed to
the external faces of the top and sides,
the bottom strip must be inside the duct.
For double layer constructions,
board joints are staggered minimum
100mm and cover strips need only to
be fixed to the inside at the bottom
of the duct. Cables should be
supported on trays but these can be
omitted if the bottom internal cover
strip are located at no more than 600mm
centres..
Supports
M10 threaded rods fixed by means of
expansion bolts
into the concrete soffit. Tensile stress in rods
should not exceed 6N/mm2. |
|
VERMICULUX®
boards can provide up to 90 minutes of fire
resistance level (FRL) for cables and services enclosure
with
external fire exposure in accordance with the criteria of BS476:
Part 20: 1987 thereby maintaining the functionality of essential
cables in a fire.
|
TABLE 3 |
Required FRL/Thickness Of
VERMICULUX® Board For Cable Enclosure |
|
FRL |
30 minutes |
60 minutes |
90 minutes |
|
Type 1 dimension |
≤100mm x 100mm |
|
Thickness |
30mm |
50mm or 2 x 25mm |
2 x 35mm |
|
Type 2 dimension |
350mm x 170mm to 760mm x
300mm |
|
Thickness |
25mm |
45mm or 20+25mm |
2 x 30mm |
|