Casing
Two layers of VERMICULUX®
board (see
TABLE 4 for thickness) edge screwed
with 60mm x 5mm wood screws at
200mm centres.
Layers offset at circumferential joints to
form 100mm overlap; boards screwed together
at the overlap with 35mm x 4mm (60
minutes), 45mm x 4mm (90 minutes) and
50mm x 4mm (120 minutes) screws at
100mm centres. The screws should be
located at the
centre of overlap. Screws must be inserted
from outside of the duct.
Supports
8mm diameter threaded rods and 15mm x
30mm x 15mm x 5 mm steel channel rails at
1220mm centres near circumferential joints.
stress on support sections should
not exceed 10N/mm2
Filler
Joints and screw heads are filled using
INTUMEX®
AN Acrylic Sealant. |
|
VERMICULUX®
boards are suitable for protecting smoke
extraction ducts in buildings where the means of escape could be
severely contaminated with smoke and become impassable.
The boards can provide
self-supporting ducts offering up to 120 minutes fire resistance level
(FRL) for stability, integrity and insulation in accordance
with the criteria of BS476: Part 24: 1987.
Maximum duct size is up to 750mm x 300mm.
|
TABLE 4 |
Required FRL/Thickness
Of VERMICULUX®
Board
For Self Supporting Ducts |
|
FRL |
60 minutes |
90 minutes |
120 minutes |
|
Thickness |
2 x 20mm |
2 x 25mm |
Internal layer
30mm,
external layer
25mm |
|